ductchecker:

"...duct smoke detectors utilizing sampling tubes shall be tested by verifying the correct pressure differential (within the manufacturers published ranges) between the inlet and exhaust tubes using a method acceptable to the manufacturer to ensure that the device will properly sample the airstream."

NFPA 72 Chapter 14 (14.4.2.2 14g(6) )
USA Flag

"...duct detectors shall be tested initially and semiannually..."

NFPA-72 Chapter 14 (14.4.2.2 14g(1) )
USA Flag

"...detector response shall be verified through the end sampling port on each pipe run; airflow through all other ports shall be verified as well."

NFPA 72 Chapter 14 (14.4.4.2.2 14g (5) )
USA Flag

"Each air duct type smoke detector shall be inspected and tested to conform operability"

CAN/ULC-S536-05,5.7.4.4.1
Canada Flag

Chaque détecteur de fumée installé dans un conduit doit être inspecté et mis à l'essai afin de confirmer qu'il est en état fonctionner

CAN/ULC S536-04, 5.7.4.4.1
Canada Flag

La circulation d'air directe et la pression différentielle à l'intérieur du tube d'analyse des détecteurs de fumée installés dans des conduits d'air doivent être mesurées afin de confirmer que leur valeur est à l'intérieur des limites prescrites par le fabricant.

CAN/ULC 5.7.4.4.2